英国EN 81-70:2003标准
EN 81-70:2003 (E)
5.2 Entrances – Door opening
5.2.1 Entrance clear opening shall be at least 800mm.
NOTE National regulations can require more than 800 mm (see Introduction) – Type 2 lifts should be provided with an entrance clear opening of 900 mm, according to ISO 4190-1:1999 (series B) and type 3 lifts with a clear opening of 1100 mm according to the same standard (see Table 1).
The car and landing doors shall be constructed as automatic power operated horizontally sliding doors.
5.2.2 Obstacle-free accessibility on the landing floors is required on all eligible floors (see Introduction, Negotiations).
5.2.3 The control system shall allow for the door dwell time to be adjustable to suit the conditions where the lift is installed (normally between 2 s and 20 s). Means to reduce this time shall be installed e.g. by using a door close button in the car. The means of the adjustment shall not be accessible to users.
5.2.4 The protection device as required by 7.5.2.1.1.3 of EN 81-1:1998 and EN 81-2:1998 shall cover the opening over the distance between at least 25 mm and 1 800 mm above the car door sill (e.g. light curtain). The device shall be a sensor which prevents physical contact between the user and the leading edges of the closing door panel(s). 5.2.4 EN81-1:1998及EN81-2:1998中7.5.2.1.1.3节所要求的安全保护装置 (如光幕) 应该覆盖电梯门区域离电梯地坎上方至少 25至 1800毫米的范围。该装置应该是一个感应器,能防止电梯使用者与关闭中的电梯门板发生接触。 |
5.3 Car dimensions, equipment in the car, stopping/leveling accuracy
5.3.1 Car dimensions
Inside dimensions of cars with a single entrance or with two opposite entrances shall be chosen in accordance with Table 1 (see Introduction, Negotiations)
Car dimensions shall be measured between the structural car walls. Any decorative finishes of a wall that reduces the minimum car dimensions given by Table 1 shall not exceed 15 mm in thickness.
Any car with adjacent entrances shall have a width and depth appropriate to allow a wheelchair user to enter and leave the car.